Zehnder ComfoAir E300/E400 Home Assistant Integration

A Home Assistant custom integration for the Zehnder ComfoAir E300/E400 ventilation unit over Modbus (RTU or TCP), with a full sensor set, alarm monitoring, and configurable notifications.

Disclaimer: This is an independent, community-built integration. It is not affiliated with, endorsed by, or supported by Zehnder. "Zehnder" and the Zehnder logo are trademarks of their respective owner, used here only to identify compatible hardware. The software is provided as-is (see LICENSE); wiring your unit and connecting a gateway is done at your own risk.

Features

  • Modbus RTU (serial) and Modbus TCP support, fully configurable through the Home Assistant UI (no YAML).
  • 40+ sensors: temperatures, humidities, fan speeds, air flows, bypass position, speed setpoints, runtime counters and more.
  • Calculated comfort sensors: absolute humidity, enthalpy, dew point (per air stream) and heat recovery efficiency.
  • Binary sensors for every alarm/warning bit reported by the unit (sensor failures, filter warning/error, pre-heater faults, bypass motor faults, frost protection).
  • Condensation limit sensor and condensation alarm: the lowest temperature that stays clear of condensation indoors, ready to use as a setpoint for underfloor cooling or a heat pump, with an optional alarm on a temperature entity of your own choosing.
  • Per-category notifications with quiet hours: connection errors, alarms and warnings each have their own mobile notify services, notification subject, delay, recovery message and quiet-hours window, as push and/or persistent notifications.
  • Fully reconfigurable afterwards via the integration's options screen - no need to remove and re-add the integration to change settings.
  • Dutch and English translations of the UI.

📦 Installation

HACS (default store)

Zehnder ComfoAir is available in the HACS default store.

Open your Home Assistant instance and open a repository inside the Home Assistant Community Store.

  1. Open HACS in Home Assistant.
  2. Search for Zehnder ComfoAir and open it (or use the button above).
  3. Click Download.
  4. Restart Home Assistant.

HACS (custom repository)

  1. Open HACS in Home Assistant.
  2. Click the three-dot menu (⋮) in the top right corner.
  3. Select Custom repositories.
  4. Add this repository URL: https://github.com/remmob/comfoair.
  5. Set the category to Integration and click Add.
  6. Search for Zehnder ComfoAir and download it.
  7. Restart Home Assistant.

See the official HACS documentation for more details.

Manual

  1. Download or copy the comfoair folder from this repository: custom_components/comfoair
  2. Place this folder in your Home Assistant installation under: config/custom_components/comfoair
  3. Restart Home Assistant.

More info and updates:

Hardware Requirements

This integration uses Modbus to connect to the Zehnder E300/E400 unit.

Display

You can use a USB to RS485 adapter to connect to the unit. The adapter should be connected to the Modbus port on the unit.
A+ to A and B- to B, if you receive no data, try to swap the A and B wires.
Or alternatively, you can use a WiFi/Ethernet to RS485 gateway, which allows you to connect to the unit wirelessly or over ethernet. Like an Elfin EW-11.

Important!

Do not use the 12V of the Zehnder unit to power your gateway or WiFi device. It can not provide enough power and can damage your device. Use a separate power supply for your gateway or WiFi device.

The integration supports both Modbus RTU (via USB) and Modbus TCP (via WiFi/Ethernet).

Adding the Integration

Go to the Integrations page in Home Assistant and click on "Add Integration". Search for "Zehnder ComfoAir" and select it.

Add ventilation unit

Give the unit a name (default: "zehnder"), used as a prefix for all its entities. The device ID cannot be changed and should be set to 1. Then choose the connection type (TCP or serial).

For a serial (Modbus RTU) connection, pick one of the available serial ports on your system. The connection settings are fixed and cannot be changed:

  • Baudrate: 19200
  • Parity: Even
  • Stopbits: 1
  • Bytesize: 8

Serial connection

For a TCP connection, provide the IP address and port of your Modbus TCP gateway. The default port is 502. Configure your Modbus RTU-to-TCP gateway with the same fixed serial settings as above.

TCP/IP connection

The last step is to select how the bypass/pre-heater is controlled: analog (0-10V), RF, or 3-way switch. This determines which registers are active; registers for the other control types stay available but inactive. You can change this later from the integration's settings.

Configuring the Integration

All settings can be changed after setup, without removing the integration. Open the integration's entry and click the gear icon.

Integration entry

This opens the settings screen, where you can change the connection details, the polling interval, the condensation settings, and the notification behavior.

Settings, part 1 Settings, part 2

ℹ️ The screenshots above still show the older settings screen; the notification options are now grouped into the collapsible sections described below.

Condensation

  • Dew point margin: safety margin above the indoor dew point. The condensation limit sensor reports the indoor dew point plus this margin: the lowest temperature that still stays clear of condensation.
  • Temperature entity for the condensation alarm (optional): pick the entity holding the flow temperature of your underfloor heating or cooling. The condensation alarm binary sensor goes off as soon as that temperature drops to or below the condensation limit. Leave it empty to only use the condensation limit sensor in your own automations.
  • Maximum change of the condensation limit (°C per hour): keeps the condensation limit sensor calm enough to feed to a heat pump as a setpoint. Showering raises the indoor humidity sharply for a couple of hours; this limits how fast the sensor may follow, so such a peak is flattened while slow changes still come through. 0 disables the limit. The condensation alarm always uses the unlimited value.

Notifications

Notifications are grouped into collapsible sections, one per category. Each category is configured independently, so a filter warning can go to a different phone than a connection error - or nowhere at all.

  • General: the shared toggle for persistent notifications (shown in the Home Assistant interface).
  • Connection errors: the Modbus connection to the unit is lost.
  • Alarms: faults of the ventilation unit, such as a sensor, fan or pre-heater error.
  • Warnings: the filter warning and the frost protection warning.

Every category has its own:

Option What it does
Notify on ... Send mobile push notifications for this category
Notify on recovery Send a follow-up message once the alarm/warning has cleared or the connection is back
Mobile notify services The notify.mobile_app_* services for this category, picked from a list or entered as a comma-separated list
Notification subject The title used for this category's notifications
Delay (seconds) The condition is re-checked after this delay before notifying, which suppresses short-lived alarms
Quiet hours Hold mobile notifications between a start and end time and deliver them once the period ends. Persistent notifications are never held

Quiet hours for warnings default to 23:00-07:00, so the filter and frost protection warnings never wake anyone up at night - the same behaviour as before, now adjustable. Quiet hours for connection errors and alarms default to off.

The device page shows the device info, all sensors and the recent alarm/warning activity:

Device info and entities

Register Table

Register Name Datatype Unit Scale Note
101 Device status uint16 - 1 0:Error;1:Initializing;2:Self Test;3:Waiting;10:Normal;20:Standby;42:Maintenance
105 Language uint16 - 1 0:NL;1:DE;2:FR;3:EN
110 Firmware version uint16 - 1 20800 = 2.8.0
111 Orientation uint16 - 1 0:Right;1:Left
112 Model uint16 - 1 0:E300 P;2:E300 RF;3:E400 RF
113 Bootloader / hardware version uint16 - 1 Packed as bootloader.hardware, e.g. 3.05
115-130 Serial number uint16 - - One ASCII character per register
300 Intake air temperature int16 °C 0.1
301 Pre-heater temperature int16 °C 0.1
303 Supply air temperature int16 °C 0.1
304 Extract air temperature int16 °C 0.1
305 Exhaust air temperature int16 °C 0.1
306 Intake air humidity uint16 % 0.1
307 Supply air humidity uint16 % 0.1
308 Extract air humidity uint16 % 0.1
309 Exhaust air humidity uint16 % 0.1
310 Extract air fan uint16 % 0.1
311 Supply air fan uint16 % 0.1
312 Extract air flow uint16 m³/h 1
313 Supply air flow uint16 m³/h 1
314 Extract air fan speed uint16 rpm 1
315 Supply air fan speed uint16 rpm 1
316 Analog voltage C1 uint16 V 0.01
317 RF voltage uint16 V 0.01
318 RF enabled uint16 - 1 0:OFF;1:ON
319 Pre-heater state uint16 - 1 0:OFF;1:ON
320 Extract air flow setpoint +- balance offset uint16 m³/h 1
321 Supply air flow setpoint uint16 m³/h 1
322 Running mean outdoor temperature int16 °C 0.1
325 Bypass motor active uint16 - 1 0:Reset bypass position;1:End position reached;2:Active
326 Bypass setpoint uint16 % 1
327 Bypass position uint16 % 1
328 0-10 V speed setting uint16 % 1 0:low;50:medium;100:high
329 RF speed setting uint16 % 1 0:low;50:medium;100:high
330 3-way switch uint16 % 1 0:low;50:medium;100:high
331 Bathroom switch uint16 - 1 0:off;100:on
334 Defrost cycles last 24h uint16 - 1
336 Runtime in days uint16 days 1
337 Fireplace present uint16 - 1 0:OFF;1:ON
338 Pre-heater present uint16 - 1 0:OFF;1:ON
344 Heat exchanger type uint16 - 1 0:HRV;1:ERV
345 Comfort humidity control uint16 - 1 0:Disabled;1:Enabled
400 Alarm bits, bank 1 uint16 - - Bitmask, see Alarm bits
402 Alarm bits, bank 2 uint16 - - Bitmask, see Alarm bits

Datatype: uint16 = unsigned 16-bit, int16 = signed 16-bit.

Scale: Value must be multiplied by this factor for real-world value.

Alarm bits

Register Bit Description
400 0 T20 temperature sensor
400 1 T21 temperature sensor
400 2 T22 temperature sensor
400 3 T11 temperature sensor
400 4 T12 temperature sensor
400 5 RH20 humidity sensor
400 6 RH22 humidity sensor
400 7 RH11 humidity sensor
400 8 RH12 humidity sensor
400 9 dp12 pressure sensor
400 10 dp22 pressure sensor
400 11 Exhaust fan speed sensor
400 12 Supply fan speed sensor
400 13 Filter warning
400 14 Filter error
402 0 Pre-heater overheat
402 1 Pre-heater location
402 2 Pre-heater error
402 3 Bypass motor extract
402 4 Bypass motor outdoor
402 5 Frost protection warning

Each bit is exposed as its own binary sensor. "Filter warning" and "Frost protection warning" belong to the Warnings notification category (quiet hours 23:00-07:00 by default); all other bits belong to the Alarms category.

Calculated sensors

These are not raw Modbus registers, but derived from the temperature/humidity registers above:

  • Absolute humidity (kg/kg) and enthalpy (kJ/kg) for the intake, supply, extract and exhaust air streams.
  • Dew point (°C) for the intake, supply, extract and exhaust air streams.
  • Condensation limit (°C): the indoor dew point (extract air) plus the configured dew point margin - the lowest temperature that stays clear of condensation. Optionally rate-limited so it can be used directly as a setpoint for underfloor cooling or a heat pump.
  • Heat recovery efficiency (%), based on supply and extract air temperatures.
  • Air flow balance (m³/h), the difference between supply and extract air flow.